Skip to main content

Equipment Specifications

Biogas Collection & Handling Specifications

HDPE gas piping, Varec pressure/vacuum relief valves, flame arresters, regenerative blowers, Eldridge flow meters, PLC controls, and waste gas burners for covered lagoon digesters.

Material Properties & Ratings

Key material specifications and rated capacities for the standard biogas collection and handling system.

PropertyUnitValueNotes
Gas Collection Piping—HDPE—
Operating Pressure (Negative)inches w/c-0.1 to -0.5—
Operating Pressure (Positive)inches w/c+0.1 to +0.4—
P/V Relief Valve Trim—316 SS—
Flame Arrester Material—316 SS—
Sediment Trap Capacitygallons6 (sediment) + 6 (condensate)—
Rated Gas Capacitycu ft/hr82,700—
Blower Type—Regenerative—
Blower Capacity (each)SCFM690 min.—
Flow Meter Rangecu ft/hr0 - 100,000—
Control Panel Rating—NEMA 4X Stainless Steel—
Waste Gas Burner Capacitycu ft/hr82,700—

Key Features

Standard features included in every EFI biogas collection and handling system.

Complete turnkey biogas collection and handling system
82,700 cu ft/hr rated capacity throughout all components
HDPE gas collection piping with central conduit layout
Varec pressure/vacuum relief with 316 SS flame arrester
Dual regenerative blowers (690 SCFM each) with flexible connectors
Eldridge thermo mass gas flow meter (0-100,000 cu ft/hr) with totalizer
Automatic waste gas burner with electric ignition and propane pilot
NEMA 4X stainless steel PLC control panel with touch screen
Time cycle and pressure-based control logic
Integrated condensate management (sediment trap, drip traps, P-traps)
Flame trap assembly with 316 SS arrester sheets

Applications

EFI biogas collection and handling systems are designed for a range of anaerobic digester and wastewater treatment applications.

Covered lagoon anaerobic digesters
Agricultural waste lagoons with biogas capture
Municipal wastewater treatment facilities
Industrial process wastewater digesters
RNG pretreatment and flare systems
Dairy, poultry, and food processing wastewater systems

Detailed Specifications

Complete equipment specifications for the standard 82,700 cu ft/hr biogas collection and handling system.

ComponentSpecification
System Rated Capacity82,700 cu ft/hr biogas
Gas Collection PipingHDPE — central conduit along lagoon centerline
P/V Relief ValveVarec Model 5810, 316 SS trim and flame arrester
Explosion Relief ValveVarec Model 7100B
Sediment/Condensate TrapVarec Model 233, welded steel, hot-dipped galvanized, 6+6 gal
Drip TrapsVarec Figure No. 246, rotating disc type, all low points
Flame Trap AssemblyVarec Model 452, 82,700 cu ft/hr, 316 SS
Pressure Relief Flame TrapVarec Model 440, 82,700 cu ft/hr, 316 SS
Pilot Line Flame CheckVarec Model 5200
BlowersRotron Model CP909, regenerative, 690 SCFM min. (qty 2)
Flow MeterEldridge thermo mass, 0-100,000 cu ft/hr with totalizer
Waste Gas BurnerVarec Model 244W, 82,700 cu ft/hr, auto electric ignition
Control PanelNEMA 4X SS, PLC, touch screen, alarm horn
Control LogicTime cycle (primary) + pressure-based (secondary)
Operating Pressure Range-0.5 to +0.4 inches w/c

Frequently Asked Questions

What is the rated gas handling capacity of EFI's standard system?
EFI's standard biogas collection and handling system is rated at 82,700 cu ft/hr throughout — from the pressure/vacuum relief valve and sediment trap through the flame trap assembly and waste gas burner. Systems are sized based on actual biogas production and can use multiple parallel units for higher volumes.
How does the pressure control system work?
The system maintains cover pressure between -0.5 and +0.4 inches water column. A Varec Model 5810 pressure/vacuum relief valve with 316 SS trim and flame arrester provides primary protection. A Varec Model 7100B explosion relief valve provides secondary protection. Blowers operate on PLC-controlled time cycles or pressure-based logic with adjustable high/low setpoints.
What type of flow metering is used?
EFI uses Eldridge thermo mass gas flow meters with a range of 0 to 100,000 cu ft/hr and totalizer function. Thermal mass flow meters provide accurate biogas measurement without requiring pressure or temperature compensation, and have no moving parts for reliable long-term operation.
How does the waste gas burner operate?
The Varec Model 244W waste gas burner has 82,700 cu ft/hr capacity with automatic electric ignition and propane pilot. The pilot operates only during waste gas flaring via a solenoid valve (fails open for safety). Pilot failure indication is displayed on the NEMA 4X control panel. During low-flow periods, one or two burners can be capped.
What daily maintenance is required?
Daily checks include: verify P-traps are full and overflowing, confirm the flare is burning properly, check igniter operation, verify normal flow on the meter, ensure the cover is not inflated, and confirm the gas equipment enclosure gate is closed and locked. Quarterly maintenance includes cleaning flare burners, verifying burners are level, and checking refractory material position.

Download Gas Collection System Specification Package

Get the complete biogas collection and handling system specification package including equipment data sheets, Varec component details, and PLC control system documentation.

Request Spec Package